Application
This product is fit for power transmission with rated voltage up to 35 kV.
Type and Designation
Basic type |
Designation |
Standard |
|
Copper core |
Al core |
||
YJV YJY YJV22 YJV32 YJV42 YJV62 YJV72 |
YJLV YJLY YJLV22 YJLV32 YJLV42 YJLV62 YJLV72 |
XLPE insulated PVC sheathed power cable |
IEC60502-2 |
Specification
Type |
Number of core |
Rated voltage Uo/U kV |
||||
3.6/6、6/6 |
6/10、8.7/10、8.7/15 |
12/20 |
18/30、21/35、26/35 |
|||
Nominal cross-section mm2 | ||||||
YJV |
YJLV |
1 |
25~630 |
25~630 |
35~630 |
50~630 |
YJV |
YJLV |
3 |
25~500 |
25~500 |
35~500 |
50~500 |
Structure Figure
Insulation thickness
Nominal cross-section |
Nominal insulation thickness at rated voltage |
||||||
3.6/6(7.2)kV |
6/6(7.2) kV |
8.7/10(12) kV |
12/20(24) kV |
18/30(36) kV |
21/35(40.5) kV |
26/35(40.5) kV |
|
25 |
2.5 |
3.4 |
4.5 |
─ |
─ |
─ |
─ |
Technical parameter
●D.C resistance of the conductor can comply with regulation in IEC60228、GB/T3956.
●Inductance and earthing capacitance.
Inductance and capacitance of single cable
Nominal cross-section |
Voltage rating kV |
|||||||||||||
3.6/6 |
6/6、6/10 |
8.7/10、8.5/15 |
12/20 |
18/30 |
21/35 |
26/35 |
||||||||
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
|
25 |
0.240 |
0.24 |
0.433 |
0.19 |
0.449 |
0.15 |
— |
— |
— |
— 0.13 |
— |
— |
— |
— |
Inductance and capacitance of 3-core cable
Nominal cross-section |
Voltage rating kV |
|||||||||||||
3.6/6 |
6/6、6/10 |
8.7/10、8.5/15 |
12/20 |
18/30 |
21/35 |
26/35 |
||||||||
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
inductance |
capacitance |
|
25 |
0.363 |
0.70 |
0.395 |
0.51 |
0.424 |
0.45 |
0.424 |
0.48 |
0.413 |
0.47 |
0.486 |
0.41 |
0.528 |
0.38 |
Other electrical performance
Rated voltage U0/U |
kV |
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
Route test |
||||||||
Partial discharge Voltage discharge≤ |
kV PC |
6.3 10 |
10.5 10 |
15.2 10 |
20.9 10 |
31.2 10 |
36.4 10 |
45.0 10 |
A.C voltage test Time |
kV min |
12.5 5 |
21 5 |
30.5 5 |
42 5 |
63 5 |
73.5 5 |
91 5 |
Type test |
||||||||
Partial discharge Voltage discharge≤ |
kV PC |
6.3 5 |
10.5 5 |
15.2 5 |
20.9 5 |
31.2 5 |
36.4 5 |
45.0 5 |
Impact voltage test |
kV |
60 |
75 |
95 |
125 |
170 |
250 |
250 |
4 hours A.C voltage test |
kV |
14.4 |
24 |
34.8 |
48 |
72 |
84 |
104 |
Feature
●XLPE insulated cable has good electrical and heat resistant performance.
●Compared with oil filled cable, it has no risk of oil leakage, and cable laying will not effected by the fall.
●It can bear long-term operating network voltage, and various over voltage encountered in the normal operating, such as over voltage by operation, by the atmosphere, by the fault.
●It can transmit the power reliable.
●It has good mechanical strength, bending, and corrosion, destroy flame-retardant performance.
●It has no pollution, and has a long usage life.
Working condition
●Max.operating temperature of the conductor:90℃.
●In short circuit condition (Max.continual period shall not exceed 5 S ), Max. temperature of the conductor shall not exceed 250℃.
●laying surrounding temperature 0℃.
●Permitted bend radius of the cable: shall not less than 15 times of outer diameter of the cable for the single cable, and shall not less than 20 times of outer diameter of the cable for three core cable.